Table 400-5(a). Allowable Ampacity for Flexible Cords and Cables. [Based on Ambient Temperature of 30 o C (86 o F) See Table 400-4.]
Source: NFPA70 - The National Electric Code
Size
(AWG) |
Thermoset Type
TS |
Thermoset Types
C, E, EO, PD, S, SJ, SJO, SJOO,
SO, SOO,
SP-1, SP-2, SP-3, SRD, SV, SVO, SVOO |
Types
HPD, HPN. S, HSJ,
HSO, SJO,
HSOO,
HSJOO |
Thermoplastic
Types TPT. TST |
Thermoplastic Types
ET, ETLB, ETP, ETT, SE, SEO,
SJE, SJEO, SJT, SJTO, SJTOO,
SPE-1, SPE-2, SPE-3, SPT-1,
SPT-2, SPT-3, ST,
SRDE, SRDT, STO, STOO,
SVE, SVEO, SVT, SVTO, SVTOO |
| |
|
A+ |
B |
|
27*
|
0.5 |
- |
- |
- |
| 20 |
- |
5** |
*** |
- |
| 18 |
- |
7 |
10 |
10 |
| 17 |
- |
- |
12 |
- |
| 16 |
- |
10 |
13 |
15 |
| 15 |
- |
- |
- |
17 |
| 14 |
- |
15 |
18 |
20 |
| 12 |
- |
20 |
25 |
30 |
| 10 |
- |
25 |
30 |
35 |
| 8 |
- |
35 |
40 |
- |
| 6 |
- |
45 |
55 |
- |
| 4 |
- |
60 |
70 |
- |
| 2 |
- |
80 |
95 |
- |
* Tinsel Cord.
** Elevator Cables Only
*** 7 amperes for elevator cables only, 2 amperes for other types
+ The allowable currents under sub-heading A apply to 3 conductor cords and other multiconductor cords connected to utilization equipment so that only 3 conductors are current carrying.
† The allowable currents under sub-heading B apply to 2 conductor cords connected to utilization equipment so that only 2 conductors are current carrying. |