On Thursday May 25th we will be upgrading our communication system. During this transition there will be a brief period of downtime with phones and email. Please feel free to contact your Territory Manager directly via cell phone or you can also contact Jack Hogarth, Inside Sales Supervisor at 203-609-1805. We apologize in advance for any inconvenience this may cause.

Lex Products


Contact Lex   LEX USA LEX UK LEX Espanol

Selection of Portable Cord

Table 400-5(a). Allowable Ampacity for Flexible Cords and Cables.
Size
(AWG)
Thermoset Type
TS
Thermoset Types
C, E, EO, PD, S, SJ, SJO, SJOO, SO, SOO, SP-1, SP-2, SP-3, SRD, SV, SVO, SVOO
Types
HPD, HPN. S, HSJ, HSO, SJO, HSOO, HSJOO
Thermoplastic
Types TPT. TST
Thermoplastic Types
ET, ETLB, ETP, ETT, SE, SEO, SJE, SJEO, SJT, SJTO, SJTOO, SPE-1, SPE-2, SPE-3, SPT-1, SPT-2, SPT-3, ST, SRDE, SRDT, STO, STOO, SVE, SVEO, SVT, SVTO, SVTOO
    A+ B†  
27*
0.5 - - -
20 - 5** *** -
18 - 7 10 10
17 - - 12 -
16 - 10 13 15
15 - - - 17
14 - 15 18 20
12 - 20 25 30
10 - 25 30 35
8 - 35 40 -
6 - 45 55 -
4 - 60 70 -
2 - 80 95 -

* Tinsel Cord.
** Elevator Cables Only
*** 7 amperes for elevator cables only, 2 amperes for other types
+ The allowable currents under sub-heading A apply to 3 conductor cords and other multiconductor cords connected to utilization equipment so that only 3 conductors are current carrying.
† The allowable currents under sub-heading B apply to 2 conductor cords connected to utilization equipment so that only 2 conductors are current carrying.